Sorter Under Speed Alarm:
Typical
Intelligrated sliding shoe sorter logic incorporates an alarm for under speed
detection that indicates insufficient cycle counts (typically at start-up) at
the first divert photoeye or setup switch photoeye.
If
inspection of the first divert photoeye is not revealing any significant
interference, Intelligrated recommends performing sorter diagnostic photoeye
detect test.
On most Intelligrated systems, this test continuously compares
cycle counts at the first divert photoeye with the remainder of the lanes.
Different screens show different results, either in relative counts or absolute
counts at each lane. In either case, problems with the first divert photoeye
should cause some kind of failure in the photoeye detect test.
This will detect a
true under speed condition (VFD not getting up to speed), but the error
threshold is typically between 1/3 and 2/3 of the expected cycle count sample
measurement. Therefore, for a drive to cause the error, the speed would be
dramatically lower than normal and visibly incorrect. If a sorter appears to be
at normal speed, the sorter VFD is not likely the cause.
1- login to momentum UI for the control Panel you have issue with
2- Navigate to I/O Diagnostics

3- locate drive control word output

4- if it showing 00 00 00 00 force the byte to 00 10 00 00
5- remove the force and ask site to restart the drive to verify the speed

Note : site need to verify the drive parameter along with that
This issue often happens due to power outage or power blip
Old ticket for refence : TS-00446172 , TS-00444486 , and TS-00471493