Problem:
An eye calibration will be needed when there are a considerable number of mistracks and belt underspeed alarms stopping the conveyor. For ACL/PandA lines a known fix is to perform an eye calibration on the line.
Environment:
MC4 Momentum.
Description:
1.- Clear the corresponding ACL/PandA line of all cartons but leave the line running/on.
2.- Hover over the conveyor icon on the left side menu and click on the "Print and Apply" menu.
3.- Select the corresponding CP on the dropdown menu at the top left corner.
4.- Select the corresponding line, click on the three dots, and select "Diagnostics".
5.- Now click on "Enable Test Mode" and then on "Diagnostics" again.
6.- Select "Eye Calibration" and then click on "Prepare to Test".
7.- Click on the "Start" button and begin the test.
7.1.- Throw one carton at a time before the 1st eye and let it run through the line.
7.2.- Once it has made it through the end of the line, all "Calibration Average (in)" values should populate and the test should also end.
7.3.- Record the values for each test.
7.4.- Repeat the test as needed, 4 cartons should be enough, and make sure you hit the "Start" button every time you throw a new one.
7.5.- Hit "Apply".
8.- Exit out of the "Eye Calibration" menu and click on "Exit Diagnostics".
9.- Run some cartons through the ACL/PandA line to test.