How to:
Replace Defective Lenze VFD (Variable Frequency Drive)
Skill required to complete this article: Controls and level is Beginner.

Question/Problem

 

How to replace a defective Lenze VFD

 

Environment

 

Induction Belts

 

Answer/Solution

 

To replace a Lenze VFD:

 

1. Turn OFF the 480 VAC following proper lockout and tagout procedures.

2. Remove the four (4) M8 mounting bolts from the VFD.

3. Remove the EPM from the defective drive unit.

4. Confirm that all dip switches are turned off on the new drive.

5. Remove the new EPM from the new drive unit and replace with the old EPM from the defective unit.

6. Reinstall the VFD, turn ON the 480 VAC, and resume operation.

 

7. If the parameter set does not automatically load, use the handheld LCP (Lenze EZAEBK2001 427D337).

8. Load parameter set 1 C0002/2 = 1 to load parameters from EPM to VFD.

a. If the drive returns a "0", the parameters have loaded successfully.

b. If the drive shows a "6", parameter C0002/16 needs to be set to “0 = inhibit controller”.

9. Inhibit controller "if required" C0002/16 = 0 to "inhibit".

10. Load parameter set 1 from above.

11. Enable controller "if required" C0002/16 = 1 to "enable".

12. Power cycle VFD 24VDC and 480VAC.

 

 

Machine generated alternative text: ÖvUiilÅy EPM —#0tary Switches  

 

If the old EPM is defective, upload the parameters from a VFD of similar belt, load it onto the new VFD and change the node address.

 

- Set C0002 to 20 to save parameters from the VFD to the keypad

- Set C0002 to 10 to load parameters from the keyboard into the VFD

- Set parameter 13899/0 to the right node address

 

 

General Instructions for setting parameters using keypad:

 

 

For transfer using the Lenze Engineer Software:

 

 

 

DISCLAIMER:

Information in this document is subject to change without notice and does not represent a commitment on the part of Intelligrated. This information is typical of the questions and general advice given; however, your particular case and circumstances may produce different results or require different recommendations. Therefore, use of this information is not a suitable replacement for contacting Intelligrated Technical Service engineering for specific recommendations and solutions to your application.

No part of this article may be reproduced or transmitted in any form or by any means including recording, or information storage and retrieval systems, for any purpose without the express written permission of Intelligrated. All information contained within the article is private and confidential and the sole property of Intelligrated.

In no event, shall Intelligrated be liable for any damages whatsoever including, without limitation, damages for loss of business profits, business interruption, loss of business information, or other pecuniary loss, even if Intelligrated has been advised of the possibility of such damages. Because some states do not allow the exclusion or limitation of liability for consequential or incidental damages, the above limitation may not apply to you.

 Related Articles
No Related Articles Available.
 Article Info
 Article ID:  KB-11389
 Published on  11/9/2022
 Last Modified on  5/10/2023
 Last Modified by  Apurba Sharma
 Original URL:  https://dashboard.intelligrated.com//Knowledgebase/Article.aspx?article=723678e1-17a5-46c7-8055-f400f1e4c024
Close Window