Question/Problem
Environment
-Allen Bradley PLC
-Shoe Sorter
Answer/Solution
Step
|
Details
|
Image/s
|
Connect to PLC
|
Connect to Sorter Control Panel PLC and be Online, make sure Calibration related AOIs are unlocked.
|
|
Back up the old Calibration Values
|
Before Starting the Calibration take the Screen shot\backup of current calibration values available in PLC program
For example current calibration values can be found under '_Calibration_of_Lanes' routine
|

'Calibration of Lanes' Rung looks similar to below,

|
Tracking Main Routine
|
To start calibration for a PLC control shoe sorter, sorter should be running without induction
To Enable the calibration toggle the 'Configure' bit on tracking main routine in PLC.
|

|
Calibration Routine on PLC
|
Navigate to Calibration routine on Sorter PLC and toggle UI_AutoCal.RunCalibration
The sorter calibration will start and count remaining will be changing until it's 0 and 'calibrationcomplete' bit is latched.
|

|
Monitor AutoCalValues
|
Monitor Auto Cal values by doing a right click and select 'monitor' on highlighted bit once calibration is complete.
|

|
Compare new and old Calibration Values.
|
Compare new calibration values after calibration with older values saved before calibration.
If difference between old and new calibration value for each lane is not more than +-1, save the new values if not then do not save new values and check the devices on the lane showing difference.
Example of new cal values are shown here.
|

|
Save New Calibration Values
|
To save the calibration values, open Instruction logic for 'AutoCalibration' AOI and find the rung for 'SaveValues' bit, toggle yellow highlighted bit so that new calibration values are saved.
|


|
Line Sorter Calibration
|
Refer Line Sorter Calibration Guide for different type of Calibration test for PLC controlled Shoe Sorter.
|
Line Sorter Calibration Guide v100 (2).pdf
|
|
|
|