How to:
PLC Controlled Shoe Sorter Calibration
Skill required to complete this article: Controls and level is No Skill Level Association.

Question/Problem

  

Environment

 

-Allen Bradley PLC

-Shoe Sorter

 

 

Answer/Solution

 

 

Step

Details

Image/s

Connect to PLC

Connect to Sorter Control Panel PLC and be Online, make sure Calibration related AOIs are unlocked.

 

Back up the old Calibration Values

Before Starting the Calibration take the Screen shot\backup of current calibration values available in PLC program

 

For example current calibration values can be found under '_Calibration_of_Lanes' routine

 

'Calibration of Lanes' Rung looks similar to below,

 

 

Tracking Main Routine

To start calibration for a PLC control shoe sorter, sorter should be running without induction

To Enable the calibration toggle the 'Configure' bit on tracking main routine in PLC.

 

 

Calibration Routine on PLC

Navigate to Calibration routine on Sorter PLC and toggle UI_AutoCal.RunCalibration

 

The sorter calibration will start and count remaining will be changing until it's 0 and 'calibrationcomplete' bit is latched.

 

Monitor AutoCalValues

Monitor Auto Cal values by doing a right click and select 'monitor' on highlighted bit once calibration is complete.

 

 

Compare new and old Calibration Values.

Compare new calibration values after calibration with older values saved before calibration.

 

If difference between old and new calibration value for each lane is not more than +-1, save the new values if not then do not save new values and check the devices on the lane showing difference.

 

Example of new cal values are shown here.

 

 

 

 

 

 

 

 

 

 

Save New Calibration Values

To save the calibration values, open Instruction logic for 'AutoCalibration' AOI and find the rung for 'SaveValues' bit, toggle yellow highlighted bit so that new calibration values are saved.

 

 

 

Line Sorter Calibration

Refer Line Sorter Calibration Guide for different type of Calibration test for PLC controlled Shoe Sorter.

 

Line Sorter Calibration Guide v100 (2).pdf

 

 

 

 

 

 

Related items

 

 

TS-00446841

 

 

 

Internal Notes

 

[Section is meant for information only available for internal use. This includes references to internal records, such as Jira tickets, bug numbers, etc.]

***If there is information in this section prior to migration to SalesForce, then it may NOT be published. This information will be fully visible along with all information above.***

 

 Related Articles
No Related Articles Available.
 Article Info
 Article ID:  KB-12675
 Published on  11/13/2024
 Last Modified on  11/13/2024
 Last Modified by  Manju Singh
 Original URL:  https://dashboard.intelligrated.com//Knowledgebase/Article.aspx?article=ae134f18-de33-41d3-9c37-7e9090bc2e0b
Close Window